Skip to simulator content

SIGNALS & CONTROL / LAB 01

4–20 mA transmitter & loop

Follow the signal. Find where the numbers stop agreeing.

VIRTUAL INSTRUMENT BENCH

Follow the live signal

Initializing

Process connection → electrical current → engineering indication

01 / PROCESS
——Gauge = normalized PV
02 / TRANSMITTER
—
Output commandIdeal: ——
03 / 4–20 mA LOOP
—
—Measured series current
04 / PLC / DCS
—Measured input currentScale: ——
05 / ENGINEERING DISPLAY
—
Engineering indication

—

Change the process value to observe the response.

Raw DCS conversion —Indication − process —

Arrows show signal progression, not electron motion. Functional diagram; not a wiring schematic.

01 / Process & transmitter
02 / PLC / DCS scale
03 / Inject a fault

Observe readings before revealing diagnostic checks.

PROCESS VALUE—Independent process reference
TRANSMITTER OUTPUT · IDEAL—From configured range
LOOP CURRENT · ACTUAL—Measured series path
DCS INDICATION—Receiver engineering value

PUT IT TO WORK

Diagnostic challenge

3 scenarios

Load a scenario, inspect the readings, then choose where to investigate first. Fault controls are hidden during a challenge.

Model assumptions & technical references

This is a linear, direct-acting, steady-state model. URV must exceed LRV. Numeric entries are bounded to ±1,000,000; process values may exceed the configured range. Units are labels: changing a unit does not convert entered numbers.

Process mode limits output to 3.8–20.5 mA as an explicit teaching convention. Real alarm/saturation settings depend on the instrument. Below 3.8 or above 20.5 mA, this receiver marks quality BAD and suppresses engineering indication; raw arithmetic remains visible. A real DCS may clamp, hold last value or use configured alarm limits. Manual and stuck modes allow 0–24 mA.

Open loop means a broken series path (0 mA actual current). The transmitter number is a command, not proof of current flow. Short / low current specifically models a bypass across the receiver sensing resistor: series current continues but input current is zero. No supply voltage, wire resistance, compliance, HART, noise, square-root extraction or process dynamics are modeled.

Zero/span faults apply only in process mode. Wrong DCS scaling loads a receiver span at half the transmitter span; endpoints remain editable. Faults are selected individually. Challenges are learning exercises; the readings do not uniquely identify every real-world fault.

NI: 4–20 mA current loop fundamentals · Emerson: transmitter saturation and alarm behavior

READ THE EVIDENCE

What’s happening?

Initializing the workbench…

Formula

mA = 4 + ((PV − LRV) / (URV − LRV)) × 16

PV = LRV + ((mA − 4) / 16) × (URV − LRV)

Field check

Compare an independent process reference, measured series current and receiver indication. A plausible engineering value can still be wrong.

Use your site’s approved isolation and test procedures. Breaking a live loop can affect plant operation.

Inspect symptoms first — reveal diagnostic checks